Program Standards

Northwest Energy Efficient Manufactured Home Program (Super Good Cents/Energy Star) Reference Standards.

Component U-Factor Requirement
Ceilings Flat U-025 (or nominal R49)
Sloped U-030 (or nominal R38)
Walls Above Grade U-052 (or nominal R21)
Floors Steady State U-033 (or nominal R33)
Windows NFRCU-Factor U-035
Area (% of floor) 15.0%
Exterior Doors U-019
Inflitration Rate 0.35 ACH
Crossover Duct Insulation R-8
Main trunk duct Fully sealed with approved mastic.

Notes:

  • The technical specifications of the Northwest Energy Efficient Manufactured Home Program can be found by visiting www.energy.state.or.us/res/manhme/manhme.htm, and click on the "Energy-Efficient Manufactured In-Plant Inspection Manual" (or click this link to download the 1MB Adobe Acrobat PDF file from our website)
  • NEEM Inflitration Rates are achieved through air sealing measures throughout the homes.You can find in the above referenced manual.
  • There are also set-up standards required by the program, including the crossover duct insulation and support, sealing the sections on installation.